Service Clearance - Belt Drive
All dimensions in inches.
Unit Size Filter Clearance Blower Clearance Cassette Clearance
1500 30 29 61
2500 31 31 64
3500 31 35 73
4500 26 41 79
5500 26 47 79
7000 30 52 92
8500 30 60 92
10000 30 60 96
Filter
Clearance
Blower
Clearance
Cassette
Access
Clearance
Handling
Lift the ERV by the
base lifting holes.
Never lift by the
weatherhood. To avoid
structural damage,
only lift the unit with all
service panels
installed.
After installing cleavis pins through all lifting holes, lift unit
a few feet off the ground and check to make sure the unit is
not tilted or twisted.
Spreader Bars
To protect unit from damage when lifting, the lifting straps
and spreader bars should be utilized as shown in figure
below. To prevent scratching of the exterior surface, pads
should be placed between the cabinet and the cables.
Lifting Holes
Cleavis
Pins
Spreader Bar